GETCO GIS Explorer
System voltage
kV
Ur
245 kV
LIWV
1050 kVp
PFWV
460 kV
Ir
3150 A
Isc
50 kA · 1 s
Break
60 ms

Module 3 · Condition monitoring

Watch SF6 density, leaks and partial discharge

Every compartment has its own temperature-compensated density monitor. Open a leak and follow the two-stage alarm into a breaker lockout, heat the hall and see why the reading does not move, then read the UHF partial-discharge pattern of four classic defects.

Gas density monitors · Line bay E-05 · bar(g) at 20 °C

Elapsed 0 yr

Alarm fascia

GZ-4 SF6 LOW · STAGE 1 REFILL
GZ-4 SF6 LOW · STAGE 2 LOCKOUT
52 TRIP / CLOSE BLOCKED
SF6 LOW · REFILL · OTHER ZONE
SF6 BELOW MIN. FUNCTIONAL
UHF PD ACTIVITY HIGH

Density trend · GZ-4 · Breaker 52

Normal
Stage 1 · refill Stage 2 · lockout

Start a leak to plot the density of the selected compartment. The time axis is compressed so a slow seal weep and a cracked casting can be compared on one screen.

UHF partial discharge · sensor S-3 on GZ-3 · phase-resolved

0 pulses / cycle