GETCO GIS Explorer
System voltage
kV
Ur
245 kV
LIWV
1050 kVp
PFWV
460 kV
Ir
3150 A
Isc
50 kA · 1 s
Break
60 ms

Module 4 · Anatomy, land and a knowledge check

Take a GIS bay apart, then test yourself

Pick any numbered component to see what it does, its typical data at the selected voltage and what to watch for in service. Explode the bay to see where the gas-tight joints are, compare the land a GIS saves against an air-insulated yard, and finish with ten questions.

Line bay elevation · 220 kV · single-phase enclosure

Side elevation of a GIS line bay with numbered components BUS-1 BUS-2 1 2 14 52 3 13 drive 4 5 6 7 8 9 LCC 10 11 12

The land a GIS gives back

A nine-bay double-busbar switchyard at 220 kV, drawn to scale. The illustrative areas include the GIS building and its gas-handling aisle.

AIS GIS
AIS yard
32,000 m²
GIS
3,200 m²
GIS share
10 %
Land saved
≈ 4.0 football pitches

GIS against AIS, point by point

AspectGas-insulated (GIS)Air-insulated (AIS)
InsulationSF6 at 4–6 bar inside earthed enclosuresAtmospheric air across open clearances
LandAbout 10–15 % of an equivalent AIS yardThe baseline
Coastal salt and desert dustLive parts sealed and unaffectedInsulator washing, flashover risk
MaintenanceInspection roughly every 8–10 years, overhaul at 20–25Frequent: isolator contacts, insulator cleaning
SafetyEvery live part enclosed and earthedExposed live parts behind safety clearances
ErectionFactory-tested modules, weeks on siteLong civil and erection work
CostHigher equipment cost, far lower land costLower equipment cost, high land cost in cities
Repair outageLonger: gas handling and module transportShorter: parts are accessible
Seismic (Kutch is zone V)Low and compact, good performanceTall porcelain is more vulnerable
EnvironmentSF6 inventory to manage — GWP about 23 500No gas insulation to manage

Knowledge check

Ten questions drawn from the four modules. Each answer comes with the reason.

Question 1 of 10

Score 0

Compared with air at the same pressure, the dielectric strength of SF6 is roughly…