Module 1 · Switching & protection
Operate a 220 kV GIS line bay, switch by switch
Click any device on the single-line diagram, or use the control panel. Interlocks refuse unsafe operations exactly as a bay controller would, current flows only when the path is closed, and the protection test trips the breaker for a real fault sequence.
Swipe the diagram sideways for the whole bay
SF6 density in the breaker compartment is below lockout — 52 is blocked for trip and close.
- Closed
- Open
- Energised
- Dead
- Earthed
- Power flow
Sequence of events
- BAYLine bay E-05 in service on Bus-1, bus coupler closed.
- GASAll eight gas compartments at rated density.
No events yet. Operate a device or run a programme and every operation, refusal and trip is logged here with its time.
The interlocking rules this bay enforces
- Disconnectors never make or break load. 89A, 89B and 89L move only with 52 open. The one exception is an on-load bus transfer: with 52-BC closed and the other bus disconnector already closed, the buses are paralleled and the disconnector only commutes current.
- No disconnector closes onto an earth. ES1 and ES2 must be open before 89A, 89B or 89L closes; FES must also be open for 89L.
- Maintenance earth switches need the breaker isolated. ES1 and ES2 close only when 89A, 89B and 89L are all open.
- The fast-acting earth switch needs a dead line. FES closes only with 89L open and no voltage on the line VT. It is rated to make full short-circuit current and to discharge trapped charge and induced current on a long line.
- The breaker needs its gas and a healthy scheme. 52 closes only with ES1 and ES2 open, the 86 lockout reset and SF6 density above the lockout set-point.
- The bus coupler holds while buses are paralleled through a bay. 52-BC cannot open while 89A and 89B are both closed, or a disconnector would be left to interrupt the bus transfer current.